Fire Extinguisher Services
Fire Extinguisher Hydrostatic Testing
DOT-Compliant Hydrostatic Testing Hydrostatic testing is a safety requirement that verifies the structural integrity of your fire extinguisher cylinders. Required every 5 or 12 years (depending on extinguisher type), this DOT-compliant process ensures your equipment is safe for continued use. During testing, the cylinder is filled with water and pressurized above normal operating levels to check for leaks, deformation, or structural weakness.
A fire extinguisher's cylinder is hydrostatically tested every 5 or 12 years, depending on its type: carbon dioxide, wet chemical (Class K), water, foam and stainless-steel dry chemical extinguishers every 5 years; dry chemical with mild-steel, brass or aluminum shells, halogenated (clean agent) and dry powder extinguishers every 12 years. The cylinder is filled with water, held at its test pressure and checked for leaks and distortion. In California, only a company licensed by the State Fire Marshal may do the test. SOS Fire Services (State Fire Marshal license E2390, CSLB C-16 #976500) tests non-DOT cylinders in its own shop, sends DOT cylinders such as CO2 to a DOT-approved test facility, and leaves loaners or pre-tested replacements until your extinguishers are back. It serves businesses across Los Angeles, Orange, Ventura and San Bernardino counties. See all fire extinguisher services.
Safety Critical
What is Hydrostatic Testing?
Hydrostatic testing is a pressure test required by California Title 19 and NFPA 10, and by the DOT for cylinders built to DOT specifications, to verify the structural integrity of fire extinguisher cylinders. Over time, cylinders can develop weaknesses from corrosion, stress, or damage that aren't visible during routine inspections.
During testing, the cylinder is filled with water and pressurized to its test pressure: the factory test pressure for stored-pressure extinguishers, or the pressure set by the DOT for DOT-specification cylinders. This safely tests the cylinder's ability to contain pressure without the risk of explosion that would occur with compressed air.
Why It Matters
A weakened cylinder can catastrophically fail under pressure, causing serious injury or death. Hydrostatic testing identifies compromised cylinders before they become dangerous.
Legal Requirement
California Title 19 §592 and NFPA 10 set the test intervals, and federal rules (49 CFR 180) apply to DOT-specification cylinders. A test that falls due in the same calendar year as the annual maintenance is done at that service.
Insurance Compliance
Fire inspectors and insurers can ask for proof of a current test. The date marked on each cylinder and our service records show it.
Cost-Effective
Testing and recharging a sound cylinder usually costs less than buying a new extinguisher. For small units we quote both, so you can choose.
Hydrostatic Testing Intervals by Type
Different extinguisher types have different testing requirements based on their construction and operating pressure.
California Title 19 §592 sets the longest allowed interval for each type in its Table 5. Cylinders built to DOT specifications are tested or replaced under DOT rules, and non-refillable disposable extinguishers are not tested; they are replaced.
5 Years
Water & Foam Extinguishers
Stored pressure water and AFFF foam extinguishers
Also antifreeze, loaded stream and FFFP foam units.
CO2 Extinguishers
Carbon dioxide high-pressure cylinders
Wet Chemical (Class K)
Kitchen fire extinguishers for cooking oils and fats
Dry Chemical (Stainless Steel)
Dry chemical extinguishers with stainless-steel shells
12 Years
Dry Chemical (ABC)
Multi-purpose ABC dry chemical units
Stored-pressure units with mild-steel, brazed-brass or aluminum shells, and cartridge-operated units with mild-steel shells. The same applies to BC and Purple-K.
Halogenated Agents
Halon, Halotron, and FE-36 clean agents
Dry Powder (Class D)
Specialized metal fire extinguishers
* CO2 extinguishers require testing every 5 years due to high operating pressures. The interval counts from the last test date marked on the cylinder, or from the manufacture date if it has never been tested.
Kitchen fire suppression system tanks are not portable extinguishers. Their tanks are tested on the manufacturer's schedule; for an ANSUL R-102 system that is every 12 years. See Ansul system service.
How to Find Your Extinguisher's Last Hydrostatic Test
The annual service tag does not show the hydrostatic test date. Look on the cylinder itself:
High-pressure cylinders (CO2)
The test month and year are stamped into the shoulder, top or neck of the cylinder. On a DOT cylinder, the tester's identification number (RIN) sits in a square between the month and the year.
Low-pressure cylinders (dry chemical, water, foam, Class K, clean agent)
A metal hydrostatic test label on the shell shows the test month and year punched out, the test pressure, and the testing company's name, address and State Fire Marshal license number. The label tears apart if someone tries to peel it off, and it may not be red.
No stamp and no label means the cylinder has not been tested since it was made, so count from its manufacture date. See what is on the annual tag.
When Is Your Next Test Due?
Enter the date on the cylinder. You get the due date right away.
Pick a type and a date to see when the test is due.
This is an estimate from the type and date you entered. A licensed technician confirms what applies to your cylinder.
Our Hydrostatic Testing Process
Professional testing performed by certified technicians using calibrated equipment in accordance with California Title 19 and, for DOT cylinders, DOT regulations.
Empty & Depressurize
Extinguisher is completely emptied and depressurized for safe testing.
Read moreShow less about Empty & Depressurize
The valve comes off and the cylinder is examined inside and out. A cylinder with pitting corrosion, damaged threads, fire damage or an old weld or solder repair is not tested; it is condemned.
Fill with Water
Cylinder is filled with water to prepare for pressure testing.
Read moreShow less about Fill with Water
Water fills it to the top of the collar. Air or gas is never used to pressure-test a cylinder.
Increase Pressure
Pressure is raised to the cylinder's test pressure over at least 30 seconds and held there for at least 30 seconds.
Inspect for Issues
Cylinder is inspected for leaks, expansion, or deformation under pressure.
Read moreShow less about Inspect for Issues
A cylinder passes when it shows no distortion or leak and the pressure holds. A DOT cylinder tested in a water jacket also fails if it keeps more than 10% of its expansion once the pressure is released.
Stamp Test Date
High-pressure cylinders are stamped with the test month and year; low-pressure cylinders get a State Fire Marshal hydrostatic test label with the month, year and test pressure.
Dry & Recharge
Passing cylinders are dried, recharged with fresh agent, and returned to service.
Read moreShow less about Dry & Recharge
Heated air used for drying may not take the shell above 150°F. The extinguisher is then recharged and gets a verification-of-service collar where one is required, and a new service tag.
Who Can Perform Hydrostatic Testing in California?
Only a company licensed by the California State Fire Marshal, with suitable test equipment and facilities, may hydrostatically test fire extinguishers. The license class matters: Type C covers low-pressure cylinders and Type E high-pressure cylinders such as CO2, and testing a cylinder built to DOT specifications also takes DOT approval as a cylinder requalifier, with its own identification number (RIN).
SOS Fire Services holds State Fire Marshal license E2390 (Type A, all classes). We test non-DOT cylinders in our own shop under that license, and DOT cylinders such as CO2 go to a DOT-approved requalification facility we partner with.
- State Fire Marshal E2390 (Type A)
- CSLB C-16 #976500
Staying Protected While Cylinders Are Tested
California does not allow an extinguisher to leave your premises for testing until a replacement rated for the same hazard is in place, and the original has to come back within 60 calendar days.
We leave a loaner of equal rating for each unit we take, and your extinguishers are usually back within 7 to 14 business days.
Complete Service
Professional Recharge Services
After hydrostatic testing, or whenever an extinguisher is discharged or shows low pressure, professional recharging restores it to full operational status. We recharge all extinguisher types with the proper agents.
- ABC Dry Chemical recharge
- BC Dry Chemical (regular & Purple K)
- CO2 cylinder refill
- Class K wet chemical recharge
- Clean agent (Halotron, FE-36) recharge
- Water and foam extinguisher refill
When to Recharge Immediately
Extinguisher has been discharged (even partially)
Pressure gauge reads below green zone
Annual inspection reveals low agent weight
After 6-year internal maintenance
Following hydrostatic testing
Visible damage to valve or seal
What Happens If a Cylinder Fails Testing?
Cylinders that fail hydrostatic testing must be condemned and cannot be returned to service. We provide:
Proper Disposal
Safe, environmentally compliant disposal of condemned cylinders.
California requires a failed cylinder to be destroyed by the owner or at the owner's direction. With your OK, we take care of it.
Replacement Options
New extinguisher recommendations matched to your needs.
We can replace a condemned unit on the same visit when we carry that type. See extinguisher sales.
Documentation
Condemnation records for your fire safety files.
A condemned extinguisher gets a red tag marked "Condemned", and a DOT cylinder that fails is also stamped with X's or "CONDEMNED". You get a record of each test, with the date, the tester's signature and the extinguisher's serial number, which Cal/OSHA requires employers to keep, and a written notice for any cylinder that is condemned.
What Affects the Cost of a Hydrostatic Test
We quote once we know what you have. The price depends on:
- Extinguisher type and size
- High-pressure (CO2) or low-pressure cylinder
- The agent it is recharged with after the test
- Parts replaced, such as valve seals and the collar
- A hose test, for units with a hose and shut-off nozzle
- How many units are due
For a small extinguisher we tell you when replacing it costs less than testing it.
Frequently Asked Questions
How do I find out when my extinguisher was last hydrostatically tested?
Look on the cylinder, not the annual tag. High-pressure cylinders such as CO2 have the test month and year stamped into the shoulder, top or neck. Low-pressure cylinders carry a metal hydrostatic test label with the month and year punched out and the test pressure. If there is neither, count from the manufacture date.
Can the test be done at my business, or does the extinguisher have to leave?
The test needs a water-filled test setup, so the cylinder leaves your site: non-DOT cylinders come to our shop, and DOT cylinders such as CO2 go to a DOT-approved test facility we partner with. Before it leaves, California requires a replacement rated for the same hazard to be in place, and the original must be back within 60 calendar days (Title 19 §591.5). We leave a loaner or a pre-tested replacement for each unit we take.
How long does a hydrostatic test take?
Your extinguishers are usually back within 7 to 14 business days, and a loaner of equal rating stays in place for each one until then.
Who is allowed to hydrostatically test a fire extinguisher in California?
A company licensed by the State Fire Marshal for that work: Type C for low-pressure cylinders, Type E for high-pressure cylinders such as CO2 (Title 19 §591.1, §595.5). A cylinder built to DOT specifications must also be tested by a DOT-approved requalifier, whose identification number (RIN) is stamped on the cylinder (49 CFR 180.205, 180.213).
Do extinguisher hoses need a hydrostatic test too?
Yes. Hose assemblies with a shut-off nozzle, and the hoses on wheeled extinguishers, are tested at the same interval as the extinguisher: CO2 hoses at 1,250 psi, dry chemical hoses at 300 psi or the service pressure, whichever is higher (Title 19 §592.2). A hose that passes needs no test record, and one that fails is destroyed (§594.5(d), §594.4(c)).
What is the difference between a hydrostatic test and six-year maintenance?
Six-year maintenance is an internal examination of stored-pressure dry chemical and dry powder extinguishers that are on a 12-year test cycle: the unit is emptied, checked inside and recharged (Title 19 §575.4). A hydrostatic test pressure-tests the cylinder itself with water, every 5 or 12 years depending on the type. A 12-year extinguisher gets both: maintenance at year 6, the test at year 12. See fire extinguisher services.
Verified reviews
What Customers Say About This Service
Overall customer rating: 5.0/5 from 151 Google and Yelp reviews.
SOS service is fast and fabulous, they are quick and efficient. I highly recommend them when you need to certify your fire extinguisher or other services. Maureen and Ashley are the best.
Read moreShow less of Jonathan Huynh's review
Zohar and his team are the best. And they guarantee their work. I 100% recommend the SOS team for any type of fire services.
Working with Zohar has been an absolute pleasure. He is always willing to answer our questions no matter how small and takes the time to explain the details of fire safety procedures and processes in an understandable way. He is also incredibly accommodating, always made sure that our needs are met--he never hesitated to fix any problem or concern that I… read more
Read moreShow less of Vyna H.'s review
Show 3 more reviewsShow fewer reviews
I own a retail store on Ventura Blvd, Encino. Fire extinguisher didn't pass inspection, this company was the ONLY one down the list that had a brand new setup for me in less then 24 hrs, in my shop, passing inspection. Super Responsive, even during early evening hours and highly recommended! Thank you for your help! Will be back for future safety needs.
Read moreShow less of M Francke Photography's review
Great service and reccomended actions. Responded to my messages and their people we polite and did a great job.
provided great service and educated us on fire protection.
Where We Provide This Service
We provide on-site service in Los Angeles, Orange, Ventura and San Bernardino counties. Share your service address and equipment details so we can confirm the work and coordinate a visit. Emergency dispatch is arranged by phone.
Request a Quote
Schedule Hydrostatic Testing
Hydrostatic testing at the 5- and 12-year marks, in our shop for non-DOT cylinders and at a DOT-approved partner facility for DOT cylinders, with condemnation records if a cylinder fails.
- Fast on-site scheduling across LA, Orange, Ventura & San Bernardino counties
- Mobile service: we come to you
- State Fire Marshal licensed technicians