Fire Extinguisher Services
On-site extinguisher maintenance, certification and replacement for your business.
- Annual inspection and tagging
- Recharge, testing and replacement
The Montclair Fire Department (MFD) and NFPA 10 require monthly visual checks logged on-site and annual CSFM recertification for commercial and multi-family properties. Extinguishers require 6-year internal maintenance and 12-year hydrostatic testing (5 years for Class K/CO2), current CSFM service tags, electronic reporting via Brycer, and placement within 75 feet of travel (30 feet for Class K).