Fire Extinguisher Services
On-site extinguisher maintenance, certification and replacement for your business.
- Annual inspection and tagging
- Recharge, testing and replacement
The Ventura Fire Department enforces state fire codes and NFPA 10 mandates for all business and multi-unit residential properties. Facilities must record monthly in-house inspections and arrange annual field servicing through a CSFM-certified company. Stored-pressure dry chemical cylinders demand 6-year internal teardowns and 12-year hydrostatic testing (shortened to 5 years for Class K and CO2 equipment). Servicing documentation is processed through Ventura's digital compliance portal (Brycer/Compliance Engine), and units must remain fully visible, properly tagged, and mounted within a 75-foot walking distance (30 feet for kitchen Class K units).