Fire Extinguisher Services
On-site extinguisher maintenance, certification and replacement for your business.
- Annual inspection and tagging
- Recharge, testing and replacement
Under the City of Colton Fire Department, the California Fire Code (CFC) and NFPA 10, all commercial and multi-family properties require monthly visual inspections logged on-site and annual professional maintenance by a California State Fire Marshal (CSFM) licensed technician. Extinguishers must undergo a 6-year internal inspection and a 12-year hydrostatic test (every 5 years for Class K and CO2 units), with reports submitted through Colton's electronic compliance tracking portal (Brycer). Units must be mounted within 75 feet of travel (30 feet for Class K in commercial kitchens) with up-to-date CSFM service tags.