• Kitchen Fire Suppression
  • Location: Pasadena
  • Completed November 2026

CaptiveAire Tank System Installation and Fire Department Acceptance Test at a Pasadena, CA Bakery

Installation and connection of a CaptiveAire tank suppression system in a new Pasadena bakery, through the permit and a Pasadena Fire Department acceptance test passed on the first visit.

Client: A new bakery kitchen · Bakery

Orange test balloons on the suppression nozzles under a CaptiveAire hood over a bakery cooking line

Project Facts

Location
Pasadena
Completed
November 2026
Facility type
Bakery
Systems
CaptiveAire tank wet chemical system · Remote manual release station · Automatic gas and electric shut-off · Alarm connection
Codes
NFPA 17A · NFPA 96 · Local fire code
Authority having jurisdiction
Pasadena Fire Department

The challenge

What the Client Needed

A new bakery in Pasadena had its CaptiveAire hood in place and needed its tank wet chemical suppression system installed, connected to the gas and electric shut-offs, permitted and accepted by the Pasadena Fire Department before the kitchen could open.

What we did

How the Job Was Done

  1. Permit

    We handled the permit with the City of Pasadena, checking the system layout and connections against the fire department's requirements before the test.

  2. Tank and piping

    The agent tank and control head were mounted and the discharge piping connected, with nozzles aimed over the cooking line, in the hood plenum and at the duct collar.

  3. Detection, manual release and shut-offs

    The thermal detection line was connected, a remote manual release station was installed on the kitchen exit path, and the automatic gas and electric shut-offs and the alarm were tied in, so a release cuts energy to the cooking line.

  4. Pre-test

    Before the inspector arrived we checked the system pressure, the detection line release, the manual release station and the shut-off response, and ran an air test with balloons on the nozzles.

  5. Fire department acceptance test

    We ran the live acceptance test with the Pasadena Fire Department inspector on site, and the system passed.

Results

The Outcome

  • Passed on the first visit

    Pasadena Fire Department acceptance with no corrections.

  • Installed, permitted and tested

    One contractor from connection to sign-off.

  • Shut-offs verified

    Gas and electric shut-off confirmed before and during the test.

Photos

On the Job

Select a photo to view it full size with its caption.

  • Orange test balloons on the suppression nozzles under a CaptiveAire hood over a bakery cooking line
    Air test before the inspection
  • CaptiveAire tank suppression push station, hood control screen and service tag on the wall
    Manual release station and tag
  • Stainless steel suppression system cabinet mounted near the ceiling
    System cabinet
  • CaptiveAire hood with nozzle drops over a six-burner range and fryer
    Finished cooking line
  • Suppression nozzle drops and filters under the CaptiveAire hood
    Nozzles under the hood

Photo 1 of 5

Orange test balloons on the suppression nozzles under a CaptiveAire hood over a bakery cooking line
Swipe for more

More of our work

See all our work →

Request a Quote

Stay Compliant. Stay Safe.

Tell us what you need and we'll get back to you within 2 hours.

  • Response within 2 hours
  • Upfront pricing, no hidden fees
  • Licensed: CSLB #976500 · Title 19

Free on-site evaluation for most jobs. We'll tell you before any charge.

By submitting, you agree to our Privacy Policy. We don't sell your information. Details you send us are used to contact you about your enquiry.