• Kitchen Fire Suppression
  • Location: Downtown Los Angeles
  • Completed November 2026

After-Hours Overhaul of a Two-Hood Ansul System in a Downtown Los Angeles High-Rise

After-hours overhaul of a two-hood Ansul system untagged since 2021: overdue cylinders swapped for hydrotested ones, new cartridges, links and caps, and a full interlock test.

Client: A restaurant in a downtown high-rise office complex · Restaurant in a high-rise office complex

Cooking line under a stainless steel hood with capped suppression nozzles after the overhaul

Project Facts

Location
Downtown Los Angeles
Completed
November 2026
Facility type
Restaurant in a high-rise office complex
Systems
Two-hood Ansul wet chemical system (3-gallon and 1.5-gallon cylinders) · Electric gas shut-off valve · Building fire alarm connection · New 6-liter Class K extinguisher
Codes
NFPA 17A · NFPA 96 · NFPA 10 · Local fire code
Authority having jurisdiction
Los Angeles Fire Department

The challenge

What the Client Needed

A restaurant in a downtown high-rise had a two-hood Ansul wet chemical system that had not been serviced or tagged since 2021. The cylinder records showed the last hydrostatic tests in 2007 on Hood 1 and 2006 on Hood 2, well past the 12-year interval, and both actuation cartridges dated from 2005. The work had to happen outside opening hours and be coordinated with the building's engineering staff.

What we did

How the Job Was Done

  1. After-hours start

    A two-technician crew came in after closing, coordinated with building engineering, and put the building fire alarm in test mode before any actuation test.

  2. Cylinder replacement

    Both overdue cylinders, 3 gallons and 1.5 gallons, were replaced with cylinders that had already passed their hydrostatic test, so the system did not have to wait for a test.

  3. New parts

    The two 2005 actuation cartridges were replaced, four new fusible links rated 360°F and 450°F went on the hood and duct detection lines, and four worn scissor link holders and a damaged 2W duct nozzle were replaced.

  4. Nozzle coverage

    The discharge piping and the appliance, plenum and duct nozzles were realigned to the system's coverage, every nozzle was cleaned, and seven new rubber blow-off caps were fitted.

  5. Class K extinguisher

    A new 6-liter wet chemical Class K extinguisher was supplied and mounted in the kitchen.

  6. Interlock test and tags

    Both hoods were actuation-tested: the electric gas shut-off valve closed and the signal reached the building's fire alarm panel. Both systems were reset and given semi-annual service tags.

Results

The Outcome

  • Five years of lapsed service closed

    Hydrotested cylinders in place, cartridges and links replaced.

  • Shut-off and alarm verified

    Gas valve closure and the building fire alarm signal tested on both hoods.

  • No lost service

    All work after hours; the restaurant opened as usual.

Photos

On the Job

Select a photo to view it full size with its caption.

  • Grease-coated fusible link holders, old blow-off caps and a nozzle removed from the hood system
    Worn parts removed
  • Cleaned discharge nozzle with a new red blow-off cap under a kitchen hood
    Nozzle with a new cap
  • Suppression nozzle with a red blow-off cap aimed down from the hood piping
    Capped nozzle after service
  • Cooking line under a stainless steel hood with capped suppression nozzles after the overhaul
    One of the two hoods after service
  • New Class K extinguisher mounted below its sign next to the manual pull station
    New Class K extinguisher and the pull station

Photo 1 of 5

Grease-coated fusible link holders, old blow-off caps and a nozzle removed from the hood system
Swipe for more

More of our work

See all our work →

Request a Quote

Stay Compliant. Stay Safe.

Tell us what you need and we'll get back to you within 2 hours.

  • Response within 2 hours
  • Upfront pricing, no hidden fees
  • Licensed: CSLB #976500 · Title 19

Free on-site evaluation for most jobs. We'll tell you before any charge.

By submitting, you agree to our Privacy Policy. We don't sell your information. Details you send us are used to contact you about your enquiry.