• Kitchen Fire Suppression
  • Location: Los Angeles
  • Completed October 2026

New Pyro-Chem 4.6-Gallon Kitchen Suppression System for a 12-Foot Hood in Los Angeles, CA

Design, plan approval, installation and fire department acceptance of a new Pyro-Chem 4.6-gallon system over a 12-foot line: stock pot, two griddles, fryer and four-burner range.

Client: A restaurant

Pyro-Chem PCL-460 cylinder and open control head mounted on the wall beside the hood

Project Facts

Location
Los Angeles
Completed
October 2026
Facility type
Restaurant
Systems
Pyro-Chem 4.6-gallon wet chemical system · Remote manual pull station · Mechanical gas shut-off valve · Black iron discharge piping
Codes
NFPA 17A · NFPA 96 · Local fire code
Authority having jurisdiction
Los Angeles Fire Department

The challenge

What the Client Needed

A restaurant was fitting a new 12-by-4-foot exhaust hood over a stock pot, two griddles, a deep fryer and a four-burner range. It needed a UL 300 wet chemical system designed for those appliances, approved by the fire department, installed and accepted before cooking could start.

What we did

How the Job Was Done

  1. Design and plan approval

    From the kitchen plans we laid out a Pyro-Chem 4.6-gallon system to the manufacturer's design rules, choosing nozzles and detector positions for each appliance, and submitted the plans to the fire department for plan check before any work on site.

  2. Cylinder and piping

    The cylinder bracket, the 4.6-gallon cylinder and the control head were mounted, and black iron discharge piping was run to nozzles over each appliance, in the hood plenum and at the duct collar.

  3. Detection, pull station and gas valve

    A detection line with fusible links was installed across the hood, a remote manual pull station was mounted on the kitchen exit path, and a mechanical gas shut-off valve was supplied so a release cuts the gas at once.

  4. Acceptance test

    We checked the pull station, the fusible link release and the gas valve closure, then ran the fire department's final acceptance inspection on site, and the system passed.

Results

The Outcome

  • One contractor, start to finish

    Design, plan check, installation and the final inspection.

  • Five appliances covered

    Stock pot, two griddles, fryer and range under one 12-foot hood.

  • Accepted by the fire department

    Cleared for cooking.

Photos

On the Job

Select a photo to view it full size with its caption.

  • Two technicians on ladders installing suppression piping above a new kitchen hood
    Piping above the hood
  • New 12-foot kitchen hood over griddles and cooking equipment during the installation
    The new hood and cooking line
  • Technician connecting piping to a newly mounted red Pyro-Chem cylinder
    Connecting the cylinder
  • Pyro-Chem PCL-460 cylinder and open control head mounted on the wall beside the hood
    Cylinder and control head

Photo 1 of 4

Two technicians on ladders installing suppression piping above a new kitchen hood
Swipe for more

More of our work

See all our work →

Request a Quote

Stay Compliant. Stay Safe.

Tell us what you need and we'll get back to you within 2 hours.

  • Response within 2 hours
  • Upfront pricing, no hidden fees
  • Licensed: CSLB #976500 · Title 19

Free on-site evaluation for most jobs. We'll tell you before any charge.

By submitting, you agree to our Privacy Policy. We don't sell your information. Details you send us are used to contact you about your enquiry.